      <TD height="30" align="middle"><SPAN ><U><strong>Installation of diesel generator set points</strong></U></SPAN> </TD> 
    </TR> 
    <TR> 
      <TD height="10" align="middle"></TD> 
    </TR> 
    <TR> 
      <TD vAlign="top"><SPAN >1, the   installation locations for a well-ventilated, generators, air inlet side should   be sufficient, diesel engine the outlet side should be good.</SPAN> <SPAN >Outlet area should be more than   1.5 times greater than the water tank area.</SPAN> <BR> 
          <SPAN > 2, the   installation should be kept clean around the ground to avoid the place in the   vicinity to produce acidic, alkaline and other </SPAN><SPAN > Fire extinguishing system should be   configured conditions.</SPAN> <BR> 
        <SPAN >3, for indoor use, must be guided through the outdoor exhaust pipe, diameter of   the muffler must be ≥ pipe diameter, the connection of the elbow pipe not more   than 3, to ensure the smooth flow of exhaust gas and the tube should be downward   5-10 degrees, to avoid the rain into; if the exhaust pipe installed vertically   upward, you must install rain cover.</SPAN> <BR> 
        <SPAN > 4, the base   with concrete, the installation shall be measured by the level of foot level   degrees, the unit fixed on the basis of the level.</SPAN> <SPAN >Between the unit and the   basis of special anti-vibration pads or should be the end of bolt.</SPAN> <BR> 
        <SPAN >5, the unit housing must be a reliable protective earth, on the need for   grounding the generator neutral point directly, it must be grounded by the   professionals in neutral, and configure the lightning protection device, non-use   of electricity in the neutral grounding device directly to ground.</SPAN> <BR> 
      <SPAN >6, the generator and   utility must be very reliable two-way switch to prevent reverse   transmission.</SPAN><SPAN >The reliability of   two-way switch wiring the electricity sector subject to the inspection of local   recognition.</SPAN> <BR></TD> 